首页|基于TRNSYS的学校建筑PV/T跨季节蓄热供暖研究

基于TRNSYS的学校建筑PV/T跨季节蓄热供暖研究

扫码查看
PV/T耦合地源热泵系统在多能互补、提高可再生能源利用率方面受到广泛的关注,针对南京市某小学工程应用PV/T耦合地源热泵系统实现跨季节供暖做模拟分析.应用TRNSYS软件针对系统的运行温度、集热效率、设备工况、能源利用率进行模拟.发现PV/T电池通过地埋管放热的冷却水具有较好的集热冷却效果;土壤蓄热体平均温度仅下降 0.23℃,实现土壤热平衡,且该系统的跨季节蓄热率约为 60%;热泵机组实际COP平均COP在 5以上,具有良好的节能效果;系统跨季节可以提供建筑热负荷的 73.17%,发电量可以满足 63.2%的热泵能耗.
Study on Cross-Season Thermal Energy Storage Heating in School Buildings Based on TRNSYS
The PV/T coupled ground source heat pump system has received wide attention in terms of multi-energy complementarity and improving the utilization rate of renewable energy.In this paper,the application of the PV/T coupled ground source heat pump system to realize inter-seasonal heating in an elementary school project in Nanjing City is simulated and analyzed.TRNSYS software is applied to simulate the system's operating temperature,heat collection efficiency,equipment working conditions,and energy utilization.It is found that the cooling water exothermic from the PV/T cell through the buried pipe has a good heat collection and cooling effect;the average temperature of the soil heat storage body decreases only by 0.23℃,realizing the soil heat balance,and the inter-seasonal heat storage rate of the system is about 60%;the average COP of the heat pump unit is above 5,which is a good energy-saving effect;the system can provide 73.17%of the heat load of the building in the inter-seasonal period,and the power generation can The system can provide 73.17%of the building heat load across seasons,and the power generation can meet 63.2%of the heat pump energy consumption.

PV/TBuried pipe thermal storageCross-season heatingTRNSYS

田亮、徐序、尹文龙、李小明、章文杰

展开 >

中铁建设集团有限公司 北京 100040

南京理工大学能源与动力工程学院 南京 210094

PV/T 地埋管蓄热 跨季节供暖 TRNSYS

&&

51920887

2024

制冷与空调(四川)
四川省制冷学会 西南交通大学

制冷与空调(四川)

CSTPCD
影响因子:0.475
ISSN:1671-6612
年,卷(期):2024.38(2)