首页|怀来两栋数据中心采用不同空调系统的对比分析

怀来两栋数据中心采用不同空调系统的对比分析

扫码查看
以实际项目为例,通过介绍张家口怀来某数字经济园区两栋数据中心的空调系统形式,分析对比水冷系统和间接蒸发冷却系统的各项指标,包括PUE、WUE、SUE、初投资、运行费用等数据,结果表明在同等建筑规模情况下,采用水冷冷冻水系统的数据中心可承载的机柜数量更多,初投资更少;而采用间接蒸发冷却空调系统的数据中心在节能、节水、运行费用方面更具优势.
Comparative Analysis of Different Air Conditioning Systems Used in Two Data Centers in Huailai
This paper takes the actual project as an example.By introducing the air-conditioning system form of two data centers in a digital economic park,this paper analyzes the indicators of comparison of water-cooled systems and indirect evaporative cooling systems,Including PUE,WUE,SUE,initial investment,operating costs,etc.,the results show that the number of cabinets that can be loaded by the data center of the water-cooled system is more,and the initial investment is less;The data center with the evaporative cooling system is more advantageous in energy conservation,water saving and operating costs.

data centerwater-cooled cold frozen water systemindirect evaporative cooling air conditioning systemPueWueeconomical analysis

于晔

展开 >

中广电广播电影电视设计研究院有限公司 北京 100045

数据中心 水冷冷冻水系统 间接蒸发冷却空调系统 PUE WUE 经济性分析

2024

制冷与空调(四川)
四川省制冷学会 西南交通大学

制冷与空调(四川)

CSTPCD
影响因子:0.475
ISSN:1671-6612
年,卷(期):2024.38(2)
  • 2