针对制冷剂R134a及其与R125的混合物,在光管及强化管外的凝结换热特性进行了试验研究.研究表明:R134a在光管外凝结换热系数的变化与Nusselt理论解相吻合;与光管相比,强化管外凝结换热系数更高,当热流密度为25 kW/m2 时,R134a的强化倍率为 15.27,而 R134a/R125 在 R125 占比分别为 6%、12%、18%下的强化倍率分别是7.45、5.74、5.38,R417A的强化倍率为6.69.对于光管,含R125 的R134a混合物凝结换热系数随热流密度的增大而减小;对于强化管,则随热流密度的增大而增大.
Experimental study of condensation heat transfer characteristics of R134a and its blends outside tubes
This experimental study investigates the condensation heat transfer properties of refriger-ant R134a and its blends,including R125,outside both a smooth tube and an enhanced tube.The re-sults show that the variation of condensation heat transfer coefficient of R134a outside the smooth tube is consistent with the Nusselt solution.When the heat flux is 25 kW/m2,the condensation heat transfer coefficient outside the enhanced tube is higher than that of the smooth tube.The enhanced ra-tio of R134a is 15.27,and the enhanced ratio of R134a/R125(the proportion of R125 is 6%,12%and 18%)is 7.45,5.74 and 5.38,respectively.The enhanced ratio of R417A was 6.69.The condensa-tion heat transfer coefficient of R134a mixture containing R125 decreases with the increase of heat flux.The condensation heat transfer coefficient increases with the increase of heat flux over the en-hanced tube.It is found that the condensation heat transfer coefficients show that the pure working medium is higher than the binary mixture,and the binary mixture is higher than the ternary working medium.

R134a/R125R417Aenhanced tubecondensation heat transfer

张定才、黄军亚、梁冰、冀文涛、郑惠敏、王长通

展开 >

中原工学院能源与环境学院 ,河南郑州 450007

西安交通大学能源与动力工程学院 ,陕西西安 710049

中原工学院图书馆 ,河南郑州 450007

中原工学院学报编辑部 ,河南郑州 450007

展开 >

R134a/R125 R417A 强化管 凝结换热

中国纺织工业联合会指导性计划河南省高等学校供热空调重点学科开放实验室研究基金

20220652015HAC203

2024

中原工学院学报
中原工学院

中原工学院学报

影响因子:0.23
ISSN:1671-6906
年,卷(期):2024.35(1)
  • 12